4421 Tradition Trail ● Plano, Texas 75093 ● 972 -964-2700 ● 800-836-7472
URL: www.iscenclosurecooling.com ● Email: iscinfo@iscsales.com
SP-ENG-210-100-09 Rev 1.6 19 | P a g e
*3Note: Refer to Electrical Schematics for further diagnostics.
Check
Setpoint. Is
Setpoint
below
ambient?
Is snowflake
LED lit on
controller?
Set Setpoint between
70 to 95 deg F
Is there voltage to
compressor? Use
meter
3
Check for faulty
evaporator fan
3
Measure Temperature at Evaporator
& Verify Heat Load Requirements. Is
unit capacity adequate for internal
head load? Possible low refrigerant.
Is compressor
thermal overload
open? Use ohm
meter.
3
Check for error code
CA,LA,HA,LA2,HA2,
P1, or P2
Check contactor
circuit. Does it have
power?
3
Refer to Alarm Signals
in Digital Temperature
Controller
Programming Section
Verify contact coil is
being activated. Check
connectivity
3
, if issue
persists component
replacement may be
needed.
Replace Thermal
Overload.